Figure 3: Corbus Wiring
Module (A) is wired correctly as it is within 1,000'/305m of the panel, in wire distance. Module (B)
is wired correctly as it is within 1,000'/305m of the panel, in wire distance. Module (C) is NOT wired
correctly as it is farther than 1,000'/305m from the panel.
Current Ratings
In order for the system to operate properly, the power output of the alarm controller and power
supply modules cannot be exceeded. Use the following data to ensure that the available current is
not exceeded.
Table 3: System Output Ratings
Device
Output
Rating (12VDC)
AUX:
700mA. Subtract the listed rating for each keypad, expansion
module and accessory connected to AUX or Corbus. At least
100mA must be reserved for the Corbus.
HS2016-4
HS2016
HS2032
HS2064
HS2064 E
HS2128
HS2128 E
BELL:
700mA. Continuous rating. 2.0A. short term. Available only
with standby battery connected. Not for use in UL/ULC or EN
certified applications.
HSM2208
AUX:
250mA. Continuous rating. Subtract for each device
connected. Subtract the total load on this terminal from the
alarm panel AUX/Corbus output.
HSM2108
AUX:
100mA. Subtract for each device connected. Subtract the total
load on this terminal from the panel AUX/Corbus output.
Alarm Controller Current Calculation
Panel Calculation
Maximum (Standby or Alarm)
25
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference