OFF – does not activate if a communications trouble condition is present.
16 - Not Networked
ON – activates if any of the following not networked conditions is present:
• Zone 001 – 128
• Keypad 01 – 16
• Siren 01 – 16
• Repeater 01 – 08
• User 01 – 1000 (wireless keys) not networked troubles
OFF – does not activate if a not networked trouble condition is present.
156 - Latched System Event
01 - True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
02 - Timed Output / Latched Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
04 - Fire Alarm
ON: activates with fire alarm, [F] key, fire zones, 2-wire smoke.
OFF: does not activate with fire alarm.
05 - Panic Alarm
ON: activates on panic alarm (audible or silent).
OFF: does not activate on panic alarm.
06 - Burglary Alarm
ON: activates on burglary alarm.
OFF: does not activate on burglary alarm.
07 - Medical Alarm
ON: activates on medical alarm.
OFF: does not activate on medical alarm.
08 - Supervisory
ON: activates on supervisory alarm.
OFF: does not activate on supervisory alarm.
09 - Priority Event
ON: activates on priority alarm.
OFF: does not activate on priority alarm.
10 - Holdup
ON: activates on holdup alarm.
OFF: does not activate on Holdup alarm.
107
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual