24-Hour Supervisory Buzzer
When tripped, the keypad buzzer emits a steady tone until a valid access code is entered.
–
Auto Verify Fire
(Hardwired smoke detectors)
When the zone is activated, a 30-second delay begins but no fire alarm sounds. If the same zone is
activated again up to 60 seconds after the delay expires, the alarm is triggered immediately. If the
same zone is activated after 60 seconds, the entire sequence begins again.
If a second fire zone is violated during the auto-verify sequence, both zones a fire alarm is
immediately triggered.
(Wireless smoke detectors)
When the zone is activated, a 40-second delay begins. The alarm is triggered if the zone is still
faulted after 30 seconds. If the zone is no longer in alarm, an 80-second verification timer begins. If
any fire zone is activated during this period, the alarm is triggered.
If another fire zone is activated during the auto verify sequence, both zones go into alarm
immediately.
Note:
Wireless smoke detectors used with this zone type must have a built in siren to act as a
pre-alert to the system alarm.
Note:
The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The
restored state of this zone type is 5.6kΩ, the alarm state is short and the trouble state is open.
–
Fire Supervisory
When this zone is tripped, the keypad buzzer activates and a supervisory alarm is sent to the
monitoring station. A valid access code must be entered to silence the buzzer.
Note:
The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The
restored state of this zone type is 5.6k, the alarm state is short and the trouble state is open.
–
24-Hour Gas
Instant alarm when activated, audible alarm at default.This zone type may be assigned to any
device type.
–
24-Hour CO
This zone type is used with CO detectors. In the event of an alarm, a distinctive siren cadence is
sounded. This is followed by a 5-second pause and then repeated. After 4 minutes, the 5-second
pause is extended to 60 seconds; however, BTO must be programmed with a value of 5 minutes or
higher. The siren is silenced when an access code is entered or the siren times out.
Note:
The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The
restored state of this zone type is 5k6, the alarm state is short and the trouble state is open.
For use with normally open contacts.
–
24-Hour Holdup
Instant alarm when activated, silent alarm at default.
Note:
Not for use in UL listed installations.
–
24-Hour Panic
Instant alarm when activated, audible alarm at default.
–
24-Hour Heat
Instant alarm when activated, audible alarm at default.
Note:
For use with normally closed contacts.
85
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual