AUX (700mA max. including PGMs 1-4)
Corbus (700mA max.)***
(Alt. Com.:125mA)
Total (must not exceed 700mA)
***See Corbus Current Calculation Chart.
For UL, ULC and Commercial Listed applications, the total standby and alarm current cannot exceed
values in Table 4 .
Table 4: Corbus Current Calculation Chart
Item
Current (mA)
x
Quantity
Total (mA)
HS2016-4/HS2016/
HS2032/HS2064/
HS2064 E/HS2128/
HS2128 E
85
x
1
85
HS2LCD
105
x
HS2ICN
105
x
HS2LED
105
x
HS2LCDP
105
x
HS2ICNP
105
x
HS2LCDRF
105
x
HS2ICNRF
105
x
HS2ICNRFP
105
x
HS2TCHP
160
x
Current required for connected devices =
HSM2300*
30
x
AUX output current of HSM2108
HSM2208*
40
x
AUX output current of HSM2208
HSM2300/2204*
35
x
HSM2HOSTx
35
x
HSM2955**
x
3G2080(R)E/
TL2803G(R)E/
TL280(R)E
125 (PCLINK)
x
Total Corbus Current =
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
26