24-Hour Medical
Instant alarm when activated, audible alarm at default.
–
24-Hour Emergency
Instant alarm when activated, audible alarm at default.
–
24-Hour Sprinkler
Instant alarm when activated, audible alarm at default.
–
24-Hour Flood
Instant alarm when activated, audible alarm at default.
–
24-Hour Latching Tamper
Instant alarm when activated, audible alarm at default. The alarm system cannot be armed until
Installer Programming is entered after the zone is restored.
–
24-Hour Non-Alarm
This zone is active at all times but does not cause an alarm. Zone attributes such as Zone Bypassing
and Door Chime affect the functionality of this zone. This zone type can also be assigned to a
temperature sensor if indoor/outdoor temperature display is required without temperature
warnings or alarm conditions.
–
24 Hour High Temperature
This zone type is used with temperature sensors and is activated when the temperature rises above
a programmed threshold (set in section [804][xxx][019-020]). Instant alarm when activated, audible
alarm at default. This zone type generates an alarm when the system is armed or disarmed.
Note:
This zone type can only be used with PGx905 wireless temperature detectors. The
temperature threshold includes a 3 °C (5-6 °F) difference between a given state and its
restored condition. For example, an alarm at 6 °C is restored at 3°C (High temperature) or 9°C
(Low temperature), depending upon the zone type selected.
The zone type for temperature sensors must be 24 Hour High/Low Temperature in order for the
sensor to operate properly.
–
24 Hour Low Temperature
This zone type is used with temperature sensors and is activated when the temperature drops
below a programmed threshold (set in section [804][xxx][019-020]). Instant alarm when activated,
audible alarm at default. This zone type generates an alarm when the system is armed or disarmed.
Note:
This zone type can only be used with PGx905 wireless temperature detectors.
–
24-Hour Non-Latching Tamper
This zone is always active and reports a tamper condition with no audible alarm when opened or
tamper/faulted.
–
Momentary Keyswitch Arm
Often used with a keyswitch module*, turning the key alternately arms and disarms the system and
silences the alarms. Tampers and faults only initiate their respective trouble sequence. The keypad
gives no indication when this zone type is activated.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
86