Ground Wiring
Figure 18: Ground Installation
Note:
Using an insulated green wire (minimum 22AWG), connect the EGND terminal on the
Corbus and the grounding wire from the building electrical installation to any of the available
holes on the back or side of the metal cabinet. See the diagram attached to the cabinet for
suggested GND point location and hardware recommendations.
Note:
Wire and installation hardware not included.
Connecting Power
Batteries
Do not connect the battery until all other wiring is complete.
Note:
A sealed, rechargeable, lead acid battery or gel type battery is required to meet UL
requirements for power standby times.
Connect the RED battery lead to the positive battery terminal and the BLACK battery lead to the
negative battery terminal.
The panel can be programmed to charge the battery at 400mA or 700mA. (
Aux Loading and Battery Selection
Battery Selection Chart
After calculating the battery capacity
(B)
for each specific installation use the following table to
determine the battery required to support the main panel in standby mode for:
• 4 hours (UL commercial burglary/residential burglary)
• 12 hours (EN50131)
• 24 hours (UL/ULC residential fire, ULC residential burglary, ULC commercial burglary, ULC
commercial fire monitoring - no bell load allowed; INCERT [Belgium])