Figure 19: LED and ICON displays
To enable or disable a toggle option, press the number key on the keypad corresponding to the
option.
Sections requiring data input, such as phone numbers, display information in a binary format using
zone LEDs 1-4 as described in the following chart:
Figure 20:
When a section is entered, the keypad immediately displays the first digit of information
programmed. Using the example in Figure 20, if zone 1 and 4 are illuminated, the first programmed
digit in the section is 9. Use the scroll key [>] to advance to the next digit.
For sections that require multiple two or three-digit numbers, the keypad beeps three times after
each entry and moves to the next item on the list. After the last digit in the section is entered, the
keypad beeps rapidly eight times and exits the programming section. The Ready light turns off and
the Armed light turns on.
To exit programming at any time, press the [#] key. All changes made up to that point are saved.
LCD Keypad
LCD keypads use a full-message display that provides visual and numerical navigation through the
programming sections. The Armed light illuminates when Installer Programming mode is activated.
Use the scroll keys to move through menu options and press [*] to select. Alternatively, enter a
specific section number. The Armed light flashes to indicate a sub-section has been selected. Press
[*] to select a sub-section. The Ready light illuminates and the information programmed in the
section is displayed.
For programming sections with toggle options, press the corresponding number on the keypad to
turn the option on or off. The display changes accordingly.
Sections requiring data input, such as phone numbers, display the full data in fields up to 32
characters long.
To input data, use the scroll keys to select a character then press the keypad button corresponding
to the number/letter required. Scroll to the next character and repeat the procedure as needed.
For information on entering HEX data, see below.
A 2-second error tone is sounded if an invalid key is pressed.
Press the [#] key to exit the program section at any time. All changes made up to that point are
saved.
Programming Hex and Decimal Data
Hexadecimal (HEX) digits may be required during programming. To program a HEX digit, press
the [*] key while in a programming section that requires a data entry. HEX programming mode
activates and the Ready light begins to flash.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
76