3/4 – Panel Low Battery Trouble/Restore
These reporting codes are transmitted when the panel battery voltage falls below 11.5VD or is
restored. These reporting codes are sent to the System Maintenance call direction group.
5/6 – Panel Battery Absent Trouble/Restore
These reporting codes are transmitted when the panel battery is not connected or is restored.
These reporting codes are sent to the System Maintenance call direction group and are transmitted
when the panel battery is detected as absent.
[302] Panel Events 2
1/2 – Bell Circuit Trouble/Restore
This reporting code is transmitted when a bell trouble condition occurs or is restored on the
system.This reporting code is sent to the System Maintenance call direction group.
3/4 – Telephone Line Trouble and Restore
This reporting code is transmitted when an alarm controller TLM trouble occurs or is restored. The
TLM trouble is communicated over an unaffected communication path if available.
This reporting code is sent to the System Maintenance call direction group.
5/6 – Auxiliary Power Supply Trouble/Restore
This reporting code is transmitted when an auxiliary voltage supply trouble occurs or is restored.
This reporting code is sent to the System Maintenance call direction group.
Note:
When the electronic fuse built in to the auxiliary power supply is tripped due to a short
or high current draw, the alarm system must be powered down then back up to reset the fuse.
[305] Panel Events 5
3/4 – PGM 2 2-Wire Trouble/Restore
This reporting code is transmitted when a trouble condition on PGM 2, configured as two-wire
smoke, occurs or is restored. This reporting code is sent to the System Maintenance call direction
group.
[311] Maintenance Events 1
1/2 – RF Jam Trouble/Restore
Sent when RF jam troubles occur/are restored. The following events cause RF jam troubles:
• Wireless repeater jamming
• RF jam
3/4 – Fire Trouble/Restore
Sent when a low sensitivity, tamper or internal fault condition/restore is detected on a wireless
smoke detector.
5 - Cold Start
Sent when power is restored to the alarm system after total power failure. The code is sent after 2
minutes to allow the alarm controller to stabilize.
6 - Delinquency
When the Delinquency option is off (
), this code is transmitted if the alarm system
has not been armed for the number of days programmed in the Delinquency Transmission Delay
(
Delinquency Transmission Delay
).
When the Delinquency option is on, this code is transmitted when no zone activity has been
detected on the system for the number of hours programmed in Delinquency Transmission Delay.