delay is already active due to an alarm on a different partition, any new activity on another partition
does not restart the communications delay timer.
Burglary verified events are postponed until after the transmission delay expires. When a valid
disarming procedure is used while the transmission delay is active, a communications canceled
message is briefly displayed on the keypad when the delay is canceled.
Note:
For UL/ULC listed installations, the entry delay plus communication delay cannot
exceed 45 seconds.
AC Failure Communication Delay (minutes or hours)
This value determines the delay before an AC failure or AC restore is reported. The AC failure or
restore is still displayed immediately. Valid entries are from 000 to 255 minutes/hours (max. 180
minutes for UL commercial installations). Selection of minutes or hours for the delay is set in
.
Note:
If AC Failure Communications Delay is programmed as 000, the AC Failure Trouble
reporting code is sent immediately.
Note:
For ULC commercial fire monitoring, the setting shall be 180 minutes.
TLM Trouble Delay
Use this section to program the number of valid checks (3 second intervals) required before
a telephone line trouble is generated. Valid entries are 000-255 for trouble annunciation and
transmission delays of 3 to 765 Seconds (12.75 Minutes).
Wireless Zone Low Battery Transmission Delay (in days)
When a zone reports a low battery condition, the trouble is indicated immediately on the keypad,
but the transmission to the monitoring station is delayed by the number of days programmed in
this section. If the low battery condition is not corrected before the delay expires, the low battery
condition is transmitted. The Low Battery Restore transmission is not delayed.
Delinquency Transmission Delay
The value in this section determines the period of time before a delinquency event is generated.
Delinquency delay is measured in days if using closing delinquency or hours if using activity
delinquency as programmed in section [311] option 6. Valid entries are [001]-[255] or [000] to
disable.
Communications Cancel Window
After the transmission Delay expires and a zone alarm is transmitted, the communications cancel
window begins.
If an access code is entered during this window, a reporting code is communicated and logged.
If the window expires without an access code entry or a code is entered after the window, the
communications canceled event is not logged or communicated.
Note:
The cancel window does not start after an [F][M][P] key alarm.
[003] – Periodic Test Transmission Cycle
This value determines the period between test transmissions. Valid entries are [000]-[255]. Whether
this interval is in hours or days is determined by section [022], option 4.
Note:
For UL residential fire installations, the test interval is 7 days.
Note:
For ULC listed installations, the test interval is 24 hours.
[004] – Periodic Test Transmission Time of Day
Enter a 4-digit time using the 24-hour clock format (HH:MM).
141
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual