7. FTC'ed events
Result
OFF: Events are communicated in the order they occur.
Note:
Must be ON for ULC commercial fire monitoring listed installations.
[382] Communicator Option 3
1 - Not Used
2 - Walk Test Communications
ON: Zone alarms that occur during Walk Test are communicated if programmed to do so.
OFF: Zone alarms during Walk Test are not communicated. FMP key alarms are still communicated.
4 - Call Waiting Cancel
ON: The call waiting cancel string (
[304] Call Waiting Cancel String
) is used on the first attempt to
dial each phone number. It is not used on any further dialing attempts.
OFF: The call waiting cancel string is not dialed.
55 - Alternate Communicator Enable/Disable
ON: The system communicates using the alternate communicator. All related programming
options, reporting and supervision are enabled when programmed via PC-Link2.
OFF: The alternate communicator and all associated programming functionality are disabled. The
auto time update feature is disabled.
Note:
If alternate communicator troubles are present when the communicator is disabled, the
troubles are logged, communicated, and cleared from [*][2]. When the communicator is re-
enabled, the trouble conditions are again logged, communicated and indicated in [*][2]. This
option must be enabled when attempting to perform a firmware upgrade using the PC-link
header.
6 - AC Failure Communication Delay in Hours/Minutes
ON: The AC failure communication delay (section [377]>[002] option 2) is programmed in hours.
OFF: The AC failure communication delay is programmed in minutes.
8 - Tamper Limit
ON: When disarmed, the system only communicates module tampers. Zone tampers are not
communicated.
OFF: When disarmed, the system communicates all tampers.
[383] Communicator Option 4
1 - Phone Number Account Code
ON: The account code communicated to the central station follows the phone number the event is
programmed to communicate on (programmed in section
• Receiver 1 all events will follow partition 1 account code
• Receiver 2 all events will follow partition 2 account code
• Receiver 3 all events will follow partition 3 account code
• Receiver 4 all events will follow partition 4 account code
OFF: Events follow the account code assigned to each partition when communicating.
145
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual