Trouble [1] Service Required
Press [01] to determine specific trouble
[08] Power Unit Failure (HSM3204CX)
A fault with the internal power supply has
been detected on the corbus repeater.
Ensure the combined output power of the corbus repeater module is not
exceeding 2A. Power cycle the module and if the trouble persists it may indicate
a permanent hardware failure.
[09] Power Unit Failure (HSM3350)
A fault with the internal power supply has
been detected on the 3A power supply.
Ensure the combined output power of the 3A power supply module is not
exceeding 3A. Power cycle the module and if the trouble persists it may indicate
a permanent hardware failure.
[10] Overcurrent
The combined output power on the panel
has exceeded 2A for a period of more than
5 minutes.
Reduce the load on the panel by re-powering modules or detectors with a
separate power supply module.
Trouble [2] Module Battery Trouble
Press [02] to determine specific trouble
Trouble
Troubleshooting
[01] Panel Low Battery
The panel detects that the battery is
below the low battery threshold (less than
11.5VDC).
Note:
This trouble condition will
not clear until the battery voltage is
12.5VDC min., under load. If battery
is new allow 1 hour to charge.
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
HSM65W power supply adapter if required.
Connect battery, remove AC power.
Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
[02] Panel No Battery
The panel detects that no battery is
present or that the battery is shorted.
Verify battery is connected.
Ensure battery leads are connected with the right polarity.
Connect battery, remove AC power.
Verify measured voltage across Aux terminals is 12.5VDC min
[04] 4 High Current output 1-4 Low Battery
(HSM2204)
HSM2204 battery less than 11.5VDC.
Note:
This trouble condition will
not clear until the battery voltage
is 12.5VDC min. under load. Charge
battery. It may be low due to a long
period without AC.
Verify voltage measured across DC input terminals is 16-18 VDC. Replace
HSM65W power supply adapter if required.
Connect battery, remove AC power.
Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
[05] 4 High Current output 1-4 No Battery
(HSM2204)
Enter 05 to view which HSM2204 does not
have a battery connected.
Verify battery is connected.
Ensure battery leads are connected with the right polarity.
Connect battery, remove AC power.
Verify measured voltage across Aux terminals is 12.5VDC min
[07] Power Supply 1-4 Low Battery
(HSM2300)
Enter 07 to view which HSM2300 has a
battery voltage less than 11.5V.
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
HSM65W power supply adapter if required.
Connect battery, remove AC power.
Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
[08] Power Supply 1-4 No Battery
(HSM2300)
Enter 08 to view which HSM2300 does not
have a battery connected.
Verify battery is connected.
Ensure battery leads are connected with the right polarity.
Connect battery, remove AC power.
Verify measured voltage across Aux terminals is 12.5VDC min
[10] HSM3204CX low battery
Enter 10 to view which HSM3204X has a
battery voltage less than 11.5V
Verify voltage measured across DC input terminals is 16-18 VAC. Replace
HSM65W power supply adapter if required.
Connect battery, remove AC power.
Verify measured voltage across Aux terminals is 12.5VDC min.
Replace battery if it is no longer able to hold a charge due to age.
225