[007] Delay Call Window
This section is used to define a user call-up window. Users can only initiate a downloading session
during this window. When a value is entered in this section, the setting in Periodic DLS Time (see
the option above) is overridden. When 00:00 is entered in this field, the alarm system initiates a DLS
call at the time programmed in Periodic DLS Time. Start and end times must be defined using 24-
hour format (e.g., 13:30) and cannot span a day (e.g., start time of 23:00 and an end time of 01:00).
Virtual Inputs
When using an alternate communicator, virtual zones can be mapped to configured system zones.
[560][001]-[032]
Assign corresponding 3 digit zone number to virtual input and then the virtual input can be
controlled by an alternate communicator. Refer to the communicator manual for more information
Schedule Programming
The sections described below are used for programming scheduled operating times for PGM
command outputs 1-4.
[601]-[604] Programming Schedule 1-4
These sections are used to define schedules for PGM command outputs 1-4 operation. When a PGM
is configured for timed output operation, it activates at the programmed start time and will turn off
after the programmed duration. For example, 5 seconds.
Each schedule contains 4 intervals, for Command Outputs 1-4. Within each interval, a start time and
end time can be programmed for each day of the week. Holiday schedules 1-4 can also be selected.
To enable the command output to follow a schedule, program the command output in section [009]
and then enter schedule 001 - 004 in section [011].
[101]-[102] Set Start Time/ End Time
Used to program the time of day the schedule interval begins and ends. (HH:MM). Valid entries
are 0000-2359 and 9999. The end time must be equal to or greater than the start time. 9999 is used
when an interval needs to extend past 24 hours. To do this, program the start time of the first
interval then the end time with 9999. Program the start time of the second interval as 9999 and the
end time with the desired time when the output should deactivate. Select the day of the week the
schedule will end.
Note:
If two intervals in a schedule are programmed with the same start time, the schedule
follows the interval with the longest end time.
[103] Days Assignment
Used to program the day of the week that the schedule interval starts and ends. Use the scroll keys
to select a day then toggle the option on. Multiple days of the week can be enabled.
[104] Holiday Assignment
Program PGMs to follow holiday schedule group 1-4. Select (Y) to enable. If all days of the week for
an interval are disabled (N), the schedule activates on the enabled holidays.
[711]-[714] Holiday Schedules
Use this section to program holiday schedules. During holiday schedules, other scheduled events
do not occur. Enter section 711 to 714 for holiday group 1 to 4.
Each of the four available holiday groups can have up to 99 holiday schedules programmed.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
150