OFF: does not activate when a battery absent trouble occurs.
165 - Prox Used
01 - True Output/Latched Output
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
166 - Partition Prox Used
01 - True Output/Latched Output
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
175 - Bell Prog Access
01 - True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
176 - Remote Operation
01 - True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
184 - Open After Alarm
01 - True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
200 - Zone Follower - Single Zone
01 - True Output/Inverted
ON: deactivated during normal operation, activated when triggered.
OFF: activated during normal operation, deactivated when triggered.
02 - Timed Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until the zone is restored.
04 - Latching
ON: output remains latched until a valid access code is entered or a valid Prox tag is presented.
OFF: output follows the setting of the Timed Output attribute.
05 - Follow Alarm
ON: output is activated on zone alarm and stays active until the bell is turned off. See table for
operation with bits 2 and 4.
OFF: output is activated on zone opening and deactivated when zone is closed.
109
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual