Low Temperature Warning
Keypads can be configured to detect low ambient temperature.
If the temperature at the keypad drops to 6° C ± 2° C (43° F ± 3°F), the keypad zone goes into alarm.
When the temperature rises above 9° C ± 2° C (48° F ± 3° F), the keypad zone is restored.
When this option is enabled, the keypad’s zone input functionality is disabled.
Refer to section [861]-[876]>[023] option 8 for more information.
Note:
This feature has not been evaluated by UL/ULC.
Keypad Function Keys
About this task:
Keypads have 5 programmable function keys that can be configured to perform one of the
following actions:
Table 17: Function Key Programming Options
[00] Null Function Key
[17] Arm Interior
[02] Instant Stay Arm
[21]-[24] Command Output 1 to 4[*][71] - [*][74]
[03] Stay Arm
[29] Bypass Group Recall
[04] Away Arm
[31] Local PGM Activate
[05] [*][9] No-Entry Arm
[32] Bypass Mode
[06] [*][4] Chime On/Off
[33] Bypass Recall
[07] System Test
[34] User Programming [*][5]
[09] Night Arm
[35] User Functions [*][6]
[12] Global Stay Arm
[37] Time & Date Program
[13] Global Away Arm
[39] Trouble Display [*][2]
[14] Global Disarming
[40] Alarm Memory [*][3]
[16] Quick Exit
[61]-[68] Partition 1 to 8 Select
To program a function key:
1. Enter Installer Programming [*][8].
2. Enter section [861] for keypad 1 function key programming.
3. Enter [001] to [005] to select a function key to program.
4. Enter a 2-digit number to assign a function key operation - [00] - [68]. See table above.
5. Continue from step 3 until all function keys are programmed.
6. Press the [#] key twice to exit Installer Programming.
Programmed function keys must be pressed for 2 seconds in order to activate the function.
Function Key Definitions
This section provides detailed descriptions of each programmable function key option.
[00] Null Function Key
This option deactivates the function key. The key does not perform any function when pressed.