OFF – does not activate if a device tamper condition is present.
12 - RF Delinquency
ON: activates if any of the following RF delinquency troubles is detected:
• zone 001 – 128
• keypad 01 – 16
• siren 01 – 16
• repeater 01 – 08
OFF – does not activate if an RF delinquency condition is present.
13 - Module Supervisory
ON – activates if any of the following module supervisory troubles is detected:
• HSM2HOST
• keypad 01 – 16
• zone expander 01 – 15
• HSM2204 1 – 4
• HSM2300 1 – 4
• HSM2208 01 – 16
OFF – does not activate if a module supervisory trouble is detected.
14 - Module Tamper
ON – activates if any of the following module tamper conditions is present:
• HSM2HOST
• Keypad 01 – 16
• Zone expander 01 – 15
• HSM2204 1 – 4
• HSM2300 1 – 4
• HSM2208 01 – 16 tamper troubles
OFF – does not activate if a module tamper condition is present.
15 - Communications
ON – activates if any of the following communications conditions is present:
• TLM trouble
• FTC receiver 1 – 4
• SIM Lock trouble
• Cellular Trouble
• Ethernet Trouble
• Receiver 1 – 4 absent
• Receiver 1 – 4 supervision trouble
• SMS Configuration trouble
• Alt comm. Fault.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
106