edge switch 2/24 service manual
2–37
Diagnostics
5
A fan module failed POSTs (indicated by a 05 FRU code) and the power supply must
be removed and replaced (See
RRP 2: Redundant Power Supply on page 4–5
).
•
This procedure is concurrent and can be performed while switch power is on.
•
Perform the data collection procedure as part of FRU removal and replacement.
Did fan module/power supply replacement solve the problem?
NO
YES
↓
The switch appears operational. Exit MAP.
Contact the next level of support. Exit MAP.
6
A power supply failed POSTs (indicated by a 06 FRU code) and must be removed and
replaced (See
RRP 2: Redundant Power Supply on page 4–5
).
•
This procedure is concurrent and can be performed while switch power is on.
•
Perform the data collection procedure as part of FRU removal and replacement.
Did power supply replacement solve the problem?
NO
YES
↓
The switch appears operational. Exit MAP.
Contact the next level of support. Exit MAP.
7
POST/IPL diagnostics detected a firmware failure (as indicated by an event code 411)
and performed an online dump. All Fibre Channel ports reset after the failure and
devices momentarily logout, login, and resume operation.
Perform the data collection procedure and return the Zip disk to HP for analysis. Exit
MAP.