4–8
edge switch 2/24 service manual
FRU Removal and Replacement
If at a web browser connected to the EWS interface, click the Log tab at the
Monitor panel. The Event Log displays. Ensure the following event codes
appear. If the event codes do not appear, go to
MAP 0000: Start MAP on page 2–6
to isolate the problem.
— 207 - Power supply installed.
— 313 - A cooling fan propeller has recovered (first fan).
— 314 - A cooling fan propeller has recovered (second fan).
— 315 - A cooling fan propeller has recovered (third fan).
— 203 - Power supply AC voltage recovery.
If at the HAFM server, open the Hardware View, click Logs, and select Event
Log. The Event Log displays. Ensure the following event codes appear. If the
event codes do not appear, go to
MAP 0000: Start MAP on page 2–6
to isolate the
problem.
— 207 - Power supply installed.
— 313 - A cooling fan propeller has recovered (first fan).
— 314 - A cooling fan propeller has recovered (second fan).
— 315 - A cooling fan propeller has recovered (third fan).
— 203 - Power supply AC voltage recovery.
7. Perform one of the following to verify power supply operation:
— If at a web browser connected to the EWS interface, open the Switch tab at
the View panel and ensure no amber LEDs illuminate that indicate a power
supply failure. If a problem is indicated, go to
MAP 0000: Start MAP on page
2–6
to isolate the problem.
— If at the HAFM server, open the Hardware View and observe the power
supply graphic to ensure no alert symbols appear that indicate a failure
(yellow triangle or red diamond). If a problem is indicated, go to
MAP 0000:
Start MAP on page 2–6
to isolate the problem.
8. Perform the data collection procedure. Refer to
Collecting Maintenance Data on
page 3–22
for instructions.