Configuration
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
124
4.4
19.30
Slip frequency actual temperature
(This is relevant at asynchronous motors with an encoder if the temperature monitoring
is active,
bits 0 to 7).
Slip frequency of the motor at nominal torque current and nominal flux (magnetic flux =
100%) according to the motor temperature actual value
. The parameter is cal-
culated by the temperature adaption characteristic and is used to determine the "Slip pre-
set value" (
Temperature adaption slip frequency
19.32
Rotor time constant
Display of the rotor time constant for the asynchronous motor; required for flux control.
The value is calculated from the magnetic current
, the nominal current
Has no significance for synchronous motors.
19.50
Notch position O.K.
19.51
Current ref. for notch position detection
Current for the notch position detection.
Standardization:
100%
=
Max. torque current
Bit
Meaning
0
Plausibility O.K. (Absolute encoder present)
1
Notch position search active
2
Notch position search ended
3
Notch position search failed or plausibility error
15 ... 4
Reserved
NOTE!
The parameter must continuously be understood as the percentage set of the "Max.
torque current"
. The parameter can be entered and displayed in ampere (this
is demanded as an auxiliary setting) at ProDrive. The value which was entered in am-
pere however can change during the operation because the reference value can
change because of the field weakening or the external total current limit. See param-
eters
and
.