![Baumuller b maXX BM2500 Operating Manual Download Page 228](http://html.mh-extra.com/html/baumuller/b-maxx-bm2500/b-maxx-bm2500_operating-manual_2711400228.webp)
Configuration
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
228
4.4
4.4.12.2 ProDrive analog input
Figure 99:
ProDrive analog input
4.4.12.3 Parameter overview
Functional block:
FbAnalogInput [144]
4.4.12.4 Description of the Parameters
144.1
Time constant PT
1
analog input 1
Time constant of the PT
1
filter for smoothing the analog input signal on Channel 1
Number
Name
Type
Min
Max
Default Value
Unit
Factor
Read
on
ly
St
o
ra
g
e
D
S
Su
pp
ort
Cycli
c
W
rite
144.1
Time constant PT1 analog
input 1
FLOAT
0
0.060
0.001
ms
1:1000
X
144.2
Scaling factor analog input 1 FLOAT
-1000000000
1000000000
1
1/V
1:1
X
144.3
Offset analog input 1
FLOAT
-10
10
0
V
1:1
X
144.4
Treshold analog input 1
FLOAT
-10
10
0
V
1:1
X
144.5
Value analog input 1
FLOAT
-23
23
0
V
1:1
X
144.6
Target number analog input
1
UDINT
0
0xFFFFFFFF 0
1:1
X
144.20
Time slot analog inputs
UINT
0
3
0
1/2/3
1:1
X