4.4
137.33
Signal length
The parameter is set at EnDat
- and Hiperface
-length measuring device ("linear en-
coders") only.
It displays the length of a signal period in the unit nm.
137.34
Measure step 1
The parameter is set at EnDat
- and Hiperface
-length measuring device ("linear en-
coders") only.
The parameter displays the measuring step which will be output from the measuring in-
trument at the serial transfer of the position value. The unit is nm.
137.36
Alarm mask
The parameter is only valid for EnDat
®
encoders.
The supported error messages of the connected encoder type are shown here.
137.37
Alarm buffer
The parameter is only valid for EnDat
®
encoders.
The error messages of the connected encoder type are displayed in this parameter. The
encoder sends an error message if the malfunction can result in wrong position values.
Bit
Supported error messages
0
1: Illumination failure
1
1: Signal amplitude
2
1: Position value
3
1: Overvoltage
4
1: Undervoltage
5
1: Overcurrent
6
1: Battery defect
Residual
Reserved