Controllers
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
516
4.7
152.8
Upper threshold relative
If the data type of the parameter selected with
is FLOAT, then this parameter
forces the upper relative switching threshold.
The relative two-level controller switches off, if the following is valid:
Parameter number actual value
parameter number relative compare value +
upper relative switch threshold
152.10
Target number
Selection of the target parameter of the relative two-level controller output.
152.11
Bit selection
Selection of the bits to be changed of the target parameter for the relative two-level con-
troller output.
152.12
Bit pattern LOW
Bit pattern which is written in the target parameter at two-level controller output LOW
(negative edge).
152.13
Bit pattern HIGH
Bit pattern which is written to the target parameter at two-level controller output HIGH
(positive edge).
152.14
Lower threshold absolute UDINT
If the data type of the parameter selected with
is INT, DINT, UINT, UDINT,
WORD or DWORD, then this parameter forces the lower absolute switching threshold.
The absolute two-level controller switches on, if the following is valid:
Parameter number actual value
lower absolute switch threshold