Description of the Software Modules and Parameters
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
517
4
152.15
Upper threshold absolute UDINT
If the data type of the parameter selected with
is INT, DINT, UINT, UDINT,
WORD or DWORD, then this parameter forces the upper absolute switching threshold.
The absolute two-level controller switches off, if the following is valid:
Parameter number actual value
upper absolute switch threshold
152.16
Lower threshold relative UDINT
If the data type of the parameter selected with
is INT, DINT, UINT, UDINT,
WORD or DWORD, then this parameter forces the lower relative switching threshold.
The relative two-level controller switches on, if the following is valid:
Parameter number actual value
parameter number relative compare value +
lower relative switch threshold
152.17
Upper threshold relative UDINT
If the data type of the parameter selected with
is INT, DINT, UINT, UDINT,
WORD or DWORD, then this parameter forces the upper relative switching threshold.
The relative two-level controller switches off, if the following is valid:
Parameter number actual value
parameter number relative compare value +
upper relative switch threshold