Dead time voltages
Dead time voltages are non-linear occurrences in the output voltage of the converter. This
can have several causes such as the locking time when switching over the IGBTs, differ-
ences of blanking times of the IGBTs and diodes and the threshold voltages of the IGBTs
and diodes. These non-linear voltages invalidate the voltage output of the PWM modula-
tor. They are considerably low compared to the nominal motor voltage. However, the en-
coderless procedures and the accuracy of power displays that are based on the motor
voltage - in particular at lower speeds - can be effected.
4.7.7.1 Parameter Overview of the Controller Adaptations
Functional blocks:
FbStromBegr [138]
Functional blocks:
FbReglerAdaption [155]
4.7.7.2 Description of the Controller Adaptations parameters
138.23
Kt correction factor
The factor (Kt
corr
) can be specified by this parameter which effects the dependence of the
torque-generating current and the displayed torque as well as the entered torque
("Torque display"
, "Torque limit symmet-
ric"
The factor effects the controller only if it reaches the Torque limit symmetric
the present values of Ks (or 1/Ks) and Kt are not effected.
The exact collaboration between the torque current and the torque is shown in
Number
Name
Type
Min
Max
Default Value
Unit
Factor
Read o
n
ly
St
o
ra
g
e
DS Supp
ort
Cyclic W
rite
138.23
Kt correction factor
FLOAT
0
100
1
1:1
X
155.1
Mode
UINT
0
0xFFFF
0
1:1
X
155.2
State
UINT
0
0xFFFF
0
1:1
X