Installation
RT-SVX24J-EN
81
Field Installed Control Wiring
The Rooftop Module (RTM) must have a mode input in
order to operate the rooftop unit.The flexibility of having
several system modes depends upon the type of sensor
and/or remote panel selected to interface with the RTM. An
overall layout of the various control options available, with
the required number of conductors for each device, is
illustrated beginning with
Figure 57, p. 87
.
Note:
All field wiring must conform to NEC guidelines as
well as state and local codes.
The various field installed control panels, sensors,
switches, and contacts discussed in this section require
both AC and DC consideration. These diagrams are
representative of standard applications and are provided
for general reference only. Always refer to the wiring
diagram that shipped with the unit for specific electrical
schematic and connection information.
Controls using 24 VAC
Before installing any connecting wiring, refer to
Figure 10,
p. 21
for the electrical access locations provided on the
unit and
Table 32, p. 81
for AC conductor sizing guidelines,
and;
a. Use copper conductors unless otherwise specified.
b. Ensure that the AC control wiring between the
controls and the unit's termination point does not
exceed three (3) ohms/conductor for the length of
the run.
Note:
Resistance in excess of 3 ohms per conductor may
cause component failure due to insufficient AC
voltage supply.
c. Be sure to check all loads and conductors for
grounds, shorts, and miswiring.
d. Do not run the AC low voltage wiring in the same
conduit with the high voltage power wiring.
Controls using DC Analog Input/Outputs
Before installing any connecting wiring between the unit
and components utilizing a DC analog input\output signal,
refer to the appropriate illustration in
Figure 10, p. 21
for
the electrical access locations provided on the unit and
Table 33, p. 81
for conductor sizing guidelines and;
e. Use standard copper conductor thermostat wire
unless otherwise specified.
f. Ensure that the wiring between the controls and the
unit termination point does not exceed two and a
half (2.5) ohms/conductor for the length of the run.
Note:
Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
g. Do not run the electrical wires transporting DC
signals in or around conduit housing high voltage
wires.
Units equipped with a Trane BACnet® Communication
Interface (BCI) or LonTalk® communication Interface (LCI)
option which utilizes a serial communication link;
a. Must be 18 AWG shielded twisted pair cable
(Belden 8760 or equivalent).
b. Must not exceed 5,000 feet maximum for each link.
Table 30. Electrical service sizing data—convenience
outlet transformer
Nominal Tons
Voltage
460
575
FLA (add) FLA (add)
90-162
3.3
2.6
Table 31. Compressor data
Unit Size
Number
of
Compress
ors
Compress
or Size
Compress
or
Designat
or
Compress
or Type
90/100 Ton Std &
Hi-Capacity
2
CSHN250
1A, 2A
Scroll
2
CSHN250
1B, 2B
Scroll
105/118 Ton Std &
Hi-Capacity
2
CSHN250
1A, 2A
Scroll
2
CSHN315
1B, 2B
Scroll
120/128 Ton Std &
Hi-Capacity
2
CSHN315
1A, 2A
Scroll
2
CSHN315
1B, 2B
Scroll
130/140 Ton Std &
Hi-Capacity
2
CSHN315
1A, 2A
Scroll
2
CSHN374
1B, 2B
Scroll
150/162 Ton Std
2
CSHN374
1A, 2A
Scroll
2
CSHN374
1B, 2B
Scroll
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Table 32. AC conductors
Distance from Unit to Control Recommended Wire Size
000-460 feet
18 gauge
461-732 feet
16 gauge
733-1000 feet
14 gauge
Table 33. DC conductors
Distance from Unit to Control Recommended Wire Size
000-150 feet
22 gauge
151- 240 feet
20 gauge
241- 385 feet
18 gauge
386- 610 feet
16 gauge
611- 970 feet
14 gauge
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...