Service and Maintenance
RT-SVX24J-EN
179
Fan Belt Adjustment
The supply fan belts and optional exhaust fan belts must
be inspected periodically to assure proper unit operation.
Replacement is necessary if the belts appear frayed or
worn. Units with dual belts require a matched set of belts
to ensure equal belt length.
When removing or installing the new belts, do not stretch
them over the sheaves. Loosen the belts using the belt
tension adjustment bolts on the motor mounting base.
Once the new belts are installed, using a Browning or
Gates tension gauge (or equivalent), see
Figure 121
,
adjust the belt tension as follows:
1. To determine the appropriate belt deflection:
a. Measure the center-to-center shaft distance (in
inches) between the fan and motor sheaves.
b. Divide the distance measured in Step 1a by 64; the
resulting value represents the amount of belt
deflection that corresponds to the proper belt
tension.
Table 57. Grease Recommendation
Recommended Grease
for Fan Bearings
Recommended
Operating Range
Exxon Unirex #2
Mobil 532
-20 F to 250 F
Mobil SHC #220
Texaco Premium RB
Table 58. Air-Cooled Condenser—Refrigerant Coil Fin Data
Tons
Coil Type
Coil Fin
Config.
Tube Dia.
Coil Rows Fins per foot
Coil Face
Area (sq. ft.)
Tube Type
90
Evaporator
Enhanced
1/2 3
168
73.75
Internally
Finned
Hi-Cap Evap
Enhanced
1/2
5
168
73.75
Internally Finned
Condenser
Enhanced
25 mm
1
240
134
Microchannel
105
Evaporator
Internally
Finned
1/2 4
168
73.75
Internally
Finned
Hi-Cap Evap
Internally
Finned
1/2
6
168
73.75
Internally Finned
Condenser
Enhanced
25 mm
1
240
161
Microchannel
120
Evaporator
Internally
Finned
1/2 3
168
106.25
Internally
Finned
Hi-Cap Evap
Internally
Finned
1/2
6
168
106.25
Internally Finned
Condenser
Enhanced
18 mm
2
276
161
Microchannel
130
Evaporator
Internally
Finned
1/2 4
168
106.25
Internally
Finned
Hi-Cap Evap
Internally
Finned
1/2
6
168
106.25
Internally Finned
Condenser
Enhanced
18 mm
2
276
161
Microchannel
150
Evaporator
Internally
Finned
1/2 6
168
106.25
Internally
Finned
Condenser
Smooth
18 mm
2
276
161
Microchannel
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could
result in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...