Service and Maintenance
RT-SVX24J-EN
183
g. Ensure parameter 14-22 Operation Mode has
reverted back to “Normal Operation”.
Notes:
•
Item 5 resets the drive to the default factory settings.
The program parameters listed in
Table 60, p. 183
will
need to be verified or changed as described in Item 3
and 4.
•
Some of the parameters listed in the Table are motor
specific. Due to various motors and efficiencies
available, use only the values stamped on the specific
motor nameplate. Do not use the Unit nameplate
values.
•
A backup copy of the current setup may be saved to the
LCP before changing parameters or resetting the drive.
See LCP Copy in the VFD Operating Instructions for
details.
6.
Follow the startup procedures for supply fan in the
“Variable Air Volume System” section or the
“Exhaust Airflow Measurement” startup procedures
for the exhaust fan.
7.
After verifying that the VFD(s) are operating
properly, press the STOP key at the Human Interface
Module to stop the unit operation.
8.
Follow the applicable steps in the “Final Unit
Checkout” section to return the unit to its normal
operating mode.
Note:
If a problem with a VFD occurs, ensure that the
programmed parameters listed for supply and
exhaust VFD
Table 60, p. 183
and
Table 61, p. 188
have been set before replacing the drive.
Monthly Maintenance
Before completing the following checks, turn the unit OFF
and lock the main power disconnect switch open.
Filters
Inspect the return air filters. Clean or replace them if
necessary. Refer to
Table 55, p. 177
and
Table 56, p. 178
for
filter information.
Cooling Season
•
[ ] Check the unit drain pans and condensate piping to
ensure that there are no blockages.
•
[ ] Inspect the evaporator and condenser coils for dirt,
bent fins, etc. If the coils appear dirty, clean them
according to the instructions described in “Coil
Cleaning” later in this section.
•
[ ] Manually rotate the condenser fans to ensure free
movement and check motor bearings for wear. Verify
that all of the fan mounting hardware is tight.
•
[ ] Inspect the F/A-R/A damper hinges and pins to
ensure that all moving parts are securely mounted.
Keep the blades clean as necessary.
Table 60. Supply and Exhaust VFD Programming Parameters
Menu
Parameter Description
Setting
Description
Load & Motor
1-21
Motor Power
Set Based on Motor Nameplate
Set only for application using 3hp motors.
Set to 2.2 kW/3 hp
1-22
Motor Voltage
Set Based on Motor Nameplate
Set only for 380/415 50 Hz applications
1-24
Motor Current
Set Based on Motor Nameplate
Sets the motor FLA
1-25
Motor Speed
Set Based on Motor Nameplate
Sets the motor RPM
Limits & Warnings
4-18
Current Limit
Rated Current 100%
Limits the maximum current to motor
Notes:
1. These parameters are motor specific and the actual motor nameplate rating must be used. Do not use the unit nameplate.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could
result in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
WARNING
Rotating Components!
During installation, testing, servicing and
troubleshooting of this product it may be necessary to
work with live and exposed rotating components. Have
a qualified or licensed service individual who has been
properly trained in handling exposed rotating
components, perform these tasks. Failure to follow all
safety precautions could result in rotating components
cutting and slashing technician which could result in
death or serious injury.
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...