Installation
RT-SVX24J-EN
77
Main Unit Power Wiring
Figure 56, p. 78
lists the field connection wire ranges for
both the main power terminal block and the optional main
power disconnect switch. The electrical tables beginning
with
Table 22, p. 79
list the component electrical data.The
electrical service must be protected from over current and
short circuit conditions in accordance with NEC
requirements. Protection devices must be sized according
to the electrical data on the nameplate. Refer to the “Power
Wire Sizing and Protection Device Equations”, for
determining;
•
the appropriate electrical service wire size based on
“Minimum Circuit Ampacity” (MCA),
•
the “Maximum Over current Protection” (MOP)
device,
•
the “Recommended Dual Element fuse size” (RDE).
1.
Location for the electrical service entrance is illustrated
in
Figure 54, p. 77
. Complete the unit power wiring
connections onto either the main terminal block, or the
factory mounted non-fused disconnect switch, inside
the unit control panel. Refer to the customer
connection diagram that shipped with the unit for
specific termination points.
2. Provide proper grounding for the unit in accordance
with local and national codes
Figure 54. Typical field power wiring
Field Supplied Survice
Over Current Protection
Pitch Pocket
Pitch Pocket
3-Wire Power
Ground
Front View Control Box
1TB1
or
1S1
Electric Heat Control Panel
Gas Heat Control Panel
Steam or Hot Water Control Panel
Heat Control Box
Condenser
Section
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...