Unit Clearances
22
RT-SVX24J-EN
Notes:
1. Stagger units to minimize span deflection which deters sound
transmission and to maximize proper diffusion of the exhaust air
before it reaches the adjacent unit outside air intake.
2. Cooling tower should be 5 feet above or 20 feet away from the outside
air intake. For additional information, see 2007 ASHRAE Handbook:
HVAC Applications, page 44.4.
Figure 11.
Multiple unit placement
Outdoor Air Intake
Outdoor Air Intake
Exhaust
Air
Outdoor Air Intake
Outdoor Air Intake
Exhaust
Air
Outdoor Air Intake
Outdoor Air Intake
Exhaust
Air
Minimum distance between units must be 16’!