RT-SVX24J-EN
173
Service and Maintenance
WARNING
Hazardous Voltage and Exposure to
Ultraviolet Radiation!
This product contains components that emit high-
intensity ultraviolet (UV-C) radiation which can be
harmful to unprotected eyes and skin. To avoid injury,
disconnect all electrical power, including remote
disconnects, and make sure the UV lights are off before
servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized.
Failure to disconnect power before servicing could
result in burns or electrocution which could result in
death or serious injury.
Trane does not recommend field installation of
ultraviolet lights in its equipment for the intended
purpose of improving indoor air quality. High intensity
C-band ultraviolet light is known to severely damage
polymer (plastic) materials and poses a personal safety
risk to anyone exposed to the light without proper
personal protective equipment. Polymer materials
commonly found in HVAC equipment that could be
susceptible include insulation on electrical wiring, fan
belts, thermal insulation, various fasteners and
bushings. Degradation of these materials can result in
serious damage to the equipment.
Trane accepts no responsibility for the performance or
operation of our equipment in which ultraviolet devices
were installed outside of the Trane factory or its
approved suppliers.
Table 50. Control Settings and Time Delays
Control Description
Elec. Designation
Contacts Open
Contacts Closed
Combustion Airflow Switch
(Gas Heat Only)
4S25
see note 1
0.1 - 0.25" wc rise in press diff
Supply Airflow Switch
(Gas Heat Only)
4S38
0.03 - 0.12" wc
0.15 + 0.05" wc rise in press diff
Freezestat
(Hydronic Heat Only)
4S12
(N.O.) Auto Reset
40 F
Gas Heat Units
Prepurge Timer: Honeywell
4U18
internal timing function
2 Stage 850/1100 MBH 60—seconds/
All other configurations—30 seconds
Sequencing Time Delay Relay
4DL6
N.C. - timed to close
60 s 20%
Notes:
The combustion airflow switch (4S25) differential is 0.02" - 0.08" wc.
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...