Service and Maintenance
RT-SVX24J-EN
175
Hz (right)
150F
175F
Low (25")
High (262.5 kW)
Downflow
215F
155F
Hz (right)
235F
155F
Low (90 kW)
Downflow
150F
175F
Hz (right)
150F
175F
Table 52. Electric Heat—Selection Limits
Table 53. Compressor Circuit Breaker Electrical Characteristics
460V
575V
380V
Unit Size
Compressor
Designator
Compressor
Size
Must
Hold
Must
Trip
Must
Hold
Must
Trip
Must
Hold
Must
Trip
90/105
1A, 2A
CSHN250
41.5
47.7
33.2
38.2
41.4
47.6
1B, 2B
CSHN250
41.5
47.7
33.2
38.2
41.4
47.6
105/118
1A, 2A
CSHN250
41.5
47.7
33.2
38.2
41.4
47.6
1B, 2B
CSHN315
54.4
62.6
43.6
50.1
54.3
62.4
120/128
1A, 2A
CSHN315
57.7
66.4
46.3
53.2
57.3
66
1B, 2B
CSHN315
54.4
62.6
43.6
50.1
54.3
62.4
130/140
1A, 2A
CSHN315
57.7
66.4
46.3
53.2
57.3
66
1B, 2B
CSHN374
63.4
72.9
50.0
57.5
63.3
72.8
150/162
1A, 2A
CSHN374
66.7
76.7
52.7
60.6
66.4
76.3
1B, 2B
CSHN374
63.4
72.9
50.0
57.5
63.3
72.8
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...