Unit Startup
130
RT-SVX24J-EN
Nom
Tons
CFM
Outside Air Bypass
Damper Open
Outside Air Bypass
Damper Closed
Exhaust Air Bypass
Damper Open
Exhaust Air Bypass
Damper Closed
130/140
9000
0.09
0.71
0.10
0.62
12000
0.15
0.97
0.18
0.92
16000
0.25
1.34
0.28
1.33
20000
0.36
-
0.40
-
23000
0.46
-
0.49
-
26000
0.57
-
0.60
-
30000
0.72
-
0.75
-
35000
0.93
-
0.97
-
40000
1.16
-
1.20
-
45000
1.40
-
1.43
-
50000
1.67
-
1.69
-
55000
1.95
-
1.96
-
58000
2.12
-
2.12
-
150/162
9000
0.09
0.71
0.10
0.62
12000
0.15
0.97
0.18
0.92
16000
0.25
1.34
0.28
1.33
20000
0.36
-
0.40
-
23000
0.46
-
0.49
-
26000
0.57
-
0.60
-
30000
0.72
-
0.75
-
35000
0.93
-
0.97
-
40000
1.16
-
1.20
-
45000
1.40
-
1.43
-
50000
1.67
-
1.69
-
55000
1.95
-
1.96
-
58000
2.12
-
2.12
-
Nom
Tons
CFM
Outside Air Bypass
Damper Open
Outside Air Bypass
Damper Closed
Exhaust Air Bypass
Damper Open
Exhaust Air Bypass
Damper Closed
Standard CFM Energy Recovery Wheel
90/100
8000
0.06
0.54
0.07
0.44
9000
0.08
0.61
0.10
0.53
10000
0.10
0.68
0.12
0.62
12000
0.15
0.83
0.17
0.77
14000
0.19
0.99
0.22
0.94
16000
0.24
1.16
0.26
1.12
18000
0.30
1.32
0.31
1.29
20000
0.35
-
0.37
-
25000
0.52
-
0.54
-
30000
0.70
-
0.73
-
33000
0.82
-
0.84
-
36000
0.95
-
0.97
-
40000
1.12
-
1.14
-
Continued on next page
Table 41. Energy recovery wheel component static pressure drops (continued)
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...