Unit Startup
132
RT-SVX24J-EN
Tons
CFM
Return Damper,
ERW only
Econo Damper,
ERW only
90/100
16000
0.14
0.15
20000
0.20
0.24
25000
0.29
0.39
30000
0.42
0.56
33000
0.51
0.69
36000
0.61
0.82
40000
0.75
1.01
105/118
19000
0.19
0.22
23000
0.25
0.33
28000
0.37
0.49
33000
0.51
0.69
38000
0.68
0.91
43000
0.87
1.17
45000
0.96
1.29
120/128
21000
0.22
0.18
26000
0.32
0.27
31000
0.45
0.39
36000
0.61
0.53
41000
0.79
0.69
46000
1.00
0.87
51000
1.24
1.07
54000
1.40
1.20
130-162
23000
0.25
0.21
26000
0.32
0.27
30000
0.42
0.36
35000
0.57
0.50
40000
0.75
0.65
45000
0.96
0.83
50000
1.19
1.02
55000
1.45
1.24
58000
1.63
1.38
Table 41. Energy recovery wheel component static pressure drops (continued)
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...