Unit Startup
146
RT-SVX24J-EN
Standard Unit with Energy Recovery
Wheel
Economizer Damper Adjustment - ERW units
Outside & Return Air Damper Operation
The outside air and return air damper actuators are
accessible through from the filter section of the unit. The
outside air and return air dampers have individual
actuators that are linked electronically. The actuators are
preset to 0 degrees from the factory. Refer to
Table 44,
p. 148
for the appropriate actuator position for the unit and
operating airflow (CFM).
To Adjust Damper Travel
1.
Drill a 1/4" hole through the unit casing up stream of
the return air dampers and below the energy recovery
wheel. Use a location that will produce an accurate
reading with the least amount of turbulence. Several
locations may be necessary, and average the reading.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK OR
UNIT DISCONNECT SWITCH.
2. Close the disconnect switch or circuit protector switch
that provides the supply power to the unit terminal
block or the unit mounted disconnect switch.
3. Turn the 115 volt control circuit switch and the 24 volt
control circuit switch to the “On” position.
4. Open the Human Interface access door, located in the
unit control panel, and press the SERVICE MODE key to
display the first service screen. Refer to the latest
edition of the applicable programming manual for
applications for the SERVICE TEST screens and
programming instructions.
5. Use Table 29, p. 77 to program the following system
components for operation by scrolling through the
displays:
Supply Fan (On)
VFD Cmd (100%, if applicable)
RTM Occ/Unocc Output
(Unoccupied)
OA Damper Pos (0%)
Outside Air Bypass Damper Pos (0%)
Exhaust Air Bypass Damper Pos (0%)
Table 43. Standard unit (no ERW) (economizer) outside
air damper travel adjustment/pressure drop
(
inches w.c.
)
Damper Position
Economizer
Linkage Set-up
1
2
3
4
5
6
Jackshaft rod
end location
1
1
2
2
2
2
Damper lever
configuration
A
B
B
B
B
B
Damper lever
rod end location
1
2
3
4
5
6
120-162 Ton w/Economizer (includes mist eliminator)
CFM
Pressure Drop (inches w.c.)
58500
0.80
1.64
2.96
-
-
-
54000
0.68
1.40
2.52
-
-
-
45500
0.48
0.99
1.79
2.22
2.62
-
42000
0.41
0.85
1.53
1.89
2.23
2.69
38000
0.34
0.69
1.25
1.55
1.83
2.20
34000
0.27
0.56
1.00
1.24
1.46
1.76
30000
0.21
0.43
0.78
0.97
1.14
1.37
90-118 Ton w/Economizer (includes mist eliminator)
CFM
Pressure Drop (inches w.c.)
47250
0.81
1.88
-
-
-
-
40500
0.60
1.39
2.62
-
-
-
36750
0.49
1.14
2.16
2.71
-
-
31500
0.36
0.84
1.59
1.99
2.36
2.87
28000
0.28
0.66
1.25
1.57
1.87
2.27
25000
0.22
0.53
1.00
1.25
1.49
1.81
23000
0.19
0.45
0.85
1.06
1.26
1.53
Damper Position
Jackshaft rod
end location
1
1
1
2
1
Damper lever
rod end location
1
2
3
5
4
Jackshaft rod
end location
1
1
1
2
1
120-162 Ton w/TRAQ™ Damper (includes mist
eliminator)
CFM
Pressure Drop (inches w.c.)
58500
1.10
1.52
2.16
2.73
54000
0.93
1.28
1.83
2.33
45500
0.64
0.89
1.28
1.64
2.14
42000
0.54
0.75
1.09
1.40
1.83
38000
0.44
0.60
0.88
1.14
1.50
34000
0.35
0.47
0.69
0.90
1.20
30000
0.27
0.35
0.53
0.69
0.93
90-118 Ton w/TRAQ™ Damper (includes mist
eliminator)
CFM
Pressure Drop (inches w.c.)
47250
1.37
1.89
2.72
40500
0.99
1.35
1.97
2.54
36750
0.80
1.09
1.60
2.08
2.74
31500
0.58
0.77
1.15
1.51
2.01
28000
0.46
0.59
0.89
1.17
1.58
25000
0.37
0.45
0.69
0.92
1.24
23000
0.31
0.37
0.57
0.76
1.04
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...