Installation
80
RT-SVX24J-EN
Table 23. Electrical service sizing data—motors
Condenser Fan Motors
Nominal
Tons
No. of Fans
460 V
575 V
380 V
FLA
FLA
FLA
90, 105
6
16.2
13.2
15
120, 130,
150
8
21.6
17.6
20
100
2
11.8
N/A
N/A
118, 128,
140, 162
2
11.8
N/A
N/A
Supply Fan Motors
Motor
Horsepow
er
460 V
575 V
380 V
FLA
FLA
FLA
15
18.5
15.1
24
20
24.7
19.6
29
25
31
24.5
38
30
36.6
29.2
47
40
49.0
39
54
50
60.5
48
68
60
71.5
57.2
81
75
90
72
103
100
115
92
N/A
Exhaust/Return Fan Motors
Motor
Horsepow
er
460 V
575 V
380 V
FLA
FLA
FLA
7.5
9.4
7.8
13.6
10
12.6
10.1
16
15
18.5
15.1
24
20
24.7
19.6
29
25
31
24.5
38
30
36.6
29.2
47
40
49.0
39
54
50
60.5
48
68
60
71.5
57.2
81
Table 24. Electrical service sizing data—electric heat
module (electric heat units only)
Voltage
460
575
380
Module kW
FLA
FLA
FLA
90 / 56
108.3
86.6
85.1
140 / 88
168.4
134.7
133.7
265 / 166
318.8
255
252.2
300 / 188
360.8
288.7
285.6
Table 25. Electrical service sizing data—control power
transformer (heating mode only)
Nominal Tons
Digit 2 Unit
Function
Voltages
460
575
380
FLA
FLA
FLA
90-150/100-162
E, L, S, X
3
3
4
90, 105/100, 118
F (850 MBH)
4
4
5
90, 105/100, 118
F (1100 MBH)
4
4
5
90, 105/100, 118
F (1800 MBH)
4
4
5
120-150/128-162
F (1100 MBH)
4
4
5
120-150/128-162
F (1800 MBH)
4
4
5
120-150/128-162
F (2500 MBH)
4
4
5
Table 26. Electrical service sizing data—crankcase heater
Nominal Tons
Voltage
460
575
380
FLA (add)
FLA
(add)
FLA
(add)
90-162
1
1
1
Table 27. Voltage utilization range
Unit Voltage
460/60/3
414-506
575/60/3
(a)
(a) Units with air-cooled condensers only.
517-633
380/50/3
(i)
342-418
Table 28. Electrical service sizing data—evaporative
condenser
Unit Part
kw
HP
Voltage
460
FLA
Pump
1.5
2.7
Sump Heater
3
3.8
Table 29. Electrical service sizing data—energy recovery
wheel motor
Nominal Tons
Unit Function
Voltages
460
575
FLA
FLA
90-128
1 (Low CFM ERW)
1.2
0.95
130-162
1 (Low CFM ERW)
1.7
1.4
90-162
2 (Std. CFM ERW)
1.7
1.4
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...