Unit Startup
158
RT-SVX24J-EN
Note:
Pile seal brackets are fixed with a single screw to
the cassette frame near the ends of the wheel
bearing beam. Because the height of the belt link is
slightly higher than that of the urethane belt, a rare
interference may occur when it passes the seal
bracket. If this occurs, remove the interfering
bracket(s). No measurable change of performance
will occur.
Seal Adjustment
1.
Disconnect all electrical power.
2. Loosen the diameter seal adjustment screws and back
the seals away from the wheel surface, see
Figure 112
.
3. Rotate the wheel clockwise until two opposing spokes
are hidden behind the bearing support beam.
4. Using a folded piece of paper as a feeler gauge,
position the paper between the wheel surface and the
diameter seals.
5. Adjust the seals toward the wheel surface until slight
friction on the paper feeler gauge is felt when the
gauge is moved along the length of the spoke.
6. Check the seal adjustment through a full rotation of the
wheel. Re-tighten the adjusting screws and recheck the
clearance with the paper-feeler gauge.
Drive Motor and Pulley Replacement
1.
Disconnect all electrical power.
2. Remove the belt from the pulley and position it
temporarily around the wheel rim.
3. Measure and record the distance from the inner edge
of the pulley to the mounting wall.
4. Loosen the set screw in the wheel drive pulley using an
Allen wrench and remove the pulley from the motor
drive shaft.
5. While supporting the weight of the drive motor in one
hand, loosen and remove the four mounting bolts.
6. Install a replacement motor with the hardware kit
supplied.
7.
Install the pulley and adjust it to the distance recorded
earlier in this procedure.
Figure 111. Retaining clip location
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Do not open the service access
doors while the unit is operating. Failure to disconnect
power before servicing could result in death or serious
injury.
Figure 112. Wheel rotation
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Do not open the service
access doors while the unit is operating. Failure to
disconnect power before servicing could result in death
or serious injury.
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...