Unit Startup
150
RT-SVX24J-EN
120/128 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees]
RA Actuator Reading [Degrees]
60
50
40
30
20
10
0
10
20
30
35
40
45
CFM
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
E/T
E/T
E/T
E/T
E/T
E/T
E/T
21000
1.48
1.02
1.63
0.84
1.02
0.76
0.83
0.72
0.81
0.70
0.68
0.51
0.50
0.47
0.44
0.38
0.33
0.28
26000
2.23
1.53
2.47
1.26
1.52
1.13
1.24
1.07
1.21
1.04
1.01
0.75
0.73
0.69
0.63
0.55
0.47
0.40
31000
2.13
1.75
2.12
1.57
1.72
1.48
1.67
1.43
1.40
1.02
0.99
0.94
0.85
0.74
0.62
0.52
36000
2.83
2.31
2.81
2.07
2.27
1.95
2.20
1.89
1.84
1.34
1.29
1.22
1.11
0.95
0.79
0.65
41000
2.95
2.63
2.89
2.47
2.80
2.39
2.33
1.68
1.62
1.53
1.38
1.18
0.98
46000
2.96
2.88
2.06
1.99
1.87
1.68
1.43
1.17
51000
2.47
2.39
2.24
2.01
1.70
1.39
54000
2.74
2.65
2.48
2.22
1.87
1.52
130-162 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees]
RA Actuator Reading [Degrees]
60
50
40
30
20
10
0
10
20
30
35
40
45
CFM
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
Econ
TRAQ
E/T
E/T
E/T
E/T
E/T
E/T
E/T
23000
1.73
1.18
1.92
0.97
1.18
0.87
0.96
0.82
0.93
0.80
0.78
0.58
0.56
0.53
0.48
0.42
0.35
0.30
26000
2.19
1.49
2.43
1.22
1.48
1.09
1.20
1.03
1.16
1.00
0.97
0.71
0.69
0.65
0.59
0.51
0.43
0.35
30000
2.89
1.95
1.59
1.94
1.42
1.56
1.34
1.52
1.29
1.26
0.91
0.88
0.83
0.75
0.64
0.54
0.44
35000
2.59
2.11
2.58
1.88
2.07
1.76
2.01
1.71
1.66
1.19
1.15
1.08
0.97
0.82
0.67
40000
2.71
2.41
2.66
2.26
2.57
2.18
2.12
1.50
1.45
1.36
1.22
1.02
0.83
45000
3.00
2.80
2.71
2.63
1.84
1.78
1.66
1.49
1.24
1.00
50000
2.23
2.15
2.01
1.79
1.49
1.19
55000
2.65
2.55
2.38
2.11
1.75
58000
2.91
2.80
2.61
2.31
1.91
T
able
44.
Standar
d
units
with
ER
W
—
field
measur
ed
plenum
pr
essur
e
(continued)
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...