Service and Maintenance
RT-SVX24J-EN
187
different times of the year.The sump water clarity should
be checked periodically.
The evaporative condenser has several design features to
reduce the possibility of biological growth in the sump.
These features include:
•
air inlets constructed to eliminate direct sunlight in the
sump
•
The sump flush sequence replenishes the sump with
fresh water 1 to 12 times per day depending on the
flush setting
•
The copper tubing in the coils is a natural biocide
Important:
Do not use chlorine tablets directly on
stainless steel surface as it can adversely
affect its corrosion resistance.
Always consult local codes for water treatment and waste
water removal requirements. Consult a water treatment
expert for water analysis and chemical treatment methods
and recommendations for specific applications.
If deemed necessary after consultation with local water
experts, there are various means of water treatment
available which can be field installed.
Microchannel Condenser Coil Repair and
Replacement
If microchannel condenser coil repair or replacement is
required, seek HVAC Knowledge Center information or
Service Guide document RT-SVB83*-EN for further details.
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...