Service and Maintenance
174
RT-SVX24J-EN
Table 51. Gas Heat—High Limit
UNIT
TONS
2500 MBH HIGH LIMIT
CONTACTS CONTACTS
FAN SIZE
(IN)
CONFIG.
OPEN
CLOSE
120-162
40
DF
195
155
40
HZ
240
200
32
DF & HORZ
220
180
1800 MBH HIGH LIMIT
120-162
32 &40
DF
240
200
32 &40
HZ
220
180
90-118
32
DF & HZ
240
200
36
DF & HZ
240
200
36
HZ
240
310
25
DF
240
200
25
HZ
220
180
1100 MBH HIGH LIMIT
120-162
32
DF
240
200
32
HZ
200
160
40
DF & HZ
240
200
90-118
32
DF
240
200
32
HZ
200
160
25 &36
DF & HZ
220
180
850 MBH HIGH LIMIT
90-118
25 &36
DF & HZ
240
200
Table 52. Electric Heat—Selection Limits
Tons
Indoor Fan
Option
Electric Heat Option
Supply
Discharge
Linear Limit -
Open Temp.
Fan Fail Limit -
Open Temp.
120-162 Ton
High (40")
High (300 kW)
Downflow
185F
185F
Hz (right)
185F
185F
Low (140 kW)
Downflow
150F
185F
Hz (right)
150F
185F
Low (32")
High (300 kW)
Downflow
205F
185F
Hz (right)
185F
185F
Low (140 kW)
Downflow
150F
185F
Hz (right)
150F
185F
105/118 Ton
High (36")
High (262.5 kW)
Downflow
195F
155F
Hz (right)
195F
155F
Low (90 kW)
Downflow
150F
175F
Hz (right)
150F
175F
Low (32")
High (262.5 kW)
Downflow
225F
185F
Hz (right)
205F
185F
Low (90 kW)
Downflow
150F
175F
Hz (right)
150F
175F
90/105 Ton
High (36")
High (262.5 kW)
Downflow
195F
155F
Hz (right)
195F
155F
Low (90 kW)
Downflow
150F
175F
Содержание SEHJ090-162
Страница 40: ...Dimensional Data 40 RT SVX24J EN Figure 13 Evaporative condenser water connection locations RIGHT SIDE VIEW ...
Страница 48: ...Installation 48 RT SVX24J EN Figure 18 Ductwork conversion ...
Страница 58: ...Installation 58 RT SVX24J EN Figure 36 5 Connected tubes 6 install panels Connected tubes 5 6 ...
Страница 75: ...Installation RT SVX24J EN 75 Figure 51 Hot water coil piping Figure 52 Steam coil piping ...
Страница 87: ...Installation RT SVX24J EN 87 Figure 57 Typical field wiring diagram for 90 to 162 ton CV control options ...
Страница 89: ...Installation RT SVX24J EN 89 Figure 59 Typical field wiring diagram for 90 to 162 ton VAV control options ...