![Sinee EM730 Series Скачать руководство пользователя страница 255](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544255.webp)
User Manual of EM730/EM730E Series Inverter
255
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F15.03
Acceleration time 2
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F15.04
Deceleration time 2
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F15.05
Acceleration time 3
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F15.06
Deceleration time 3
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F15.07
Acceleration time 4
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F15.08
Deceleration time 4
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F15.09
Fundamental
frequency of
acceleration and
deceleration time
0: maximum frequency F00.16
1: 50.00Hz
2: set frequency
0
〇
The system has four groups (F00.14 and F00.15 in the first group) of acceleration and
deceleration time options to meet different needs for normal operation. After completing the
setting, the user can switch them via the combination of digital input functions “19: acceleration
and deceleration time terminal 1” and “20: acceleration and deceleration time terminal 2”. For
details, please see: Table 7-6 Function List of Multi-function Digital Input Terminals.
Output frequency
0
Fundamental
frequency of
acceleration and
deceleration time
F15.09
Set deceleration time
Set acceleration
time
Actual acceleration time
Actual deceleration time
Set frequency
Time t
Fig. 7-33 Schematic Diagram of Acceleration and Deceleration Time