User Manual of EM730/EM730E Series Inverter
224
Time
Output
frequency
0
Initial PID
value
(F09.14)
Holding time of initial
PID value (F09.15)
Fig. 9-29 Schematic Diagram of Initial PID Output
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F09.16
Upper limit of PID
output
F09.17 - +100.0
%
100.0
●
F09.17
Lower limit of PID
output
–100.0 - F09.16
%
0.0
●
The PID output is limited. The output range of the PID module in the whole process is
(F09.17, F09.16). That is, if the actual adjustment result is beyond this range, the output will be
based on the boundaries.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F09.18 PID deviation limit 0.00-100.00 (0.00: invalid)
%
0.00
●
When the deviation between the PID setting and feedback is less than or equal to the
deviation limit (F09.18), the PID will stop the adjustment. When the deviation between the
setting and feedback is smaller, the output frequency will remain stable. This is valid for some
closed-loop control applications.