User Manual of EM730/EM730E Series Inverter
275
F17.35
VY4 valid delay
time
0.000-30.000
s
0.000
●
F17.36
VY4 invalid delay
time
0.000-30.000
s
0.000
●
The terminals VY1 to VY8 essentially have the same function, but there are no
corresponding physical terminals actually. They all have the positive and negative logic
functions. The terminals VY1 to VY4 have the delay function, and their statuses can be
confirmed in the same way. They can be set separately. The terminal VY1 is taken as an
example below.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F17.28
Control options of
virtual output
terminal
D7
D6
D5
D4
D3
D2
D1
D0
111
11111
〇
VY8 VY7 VY6 VY5 VY4 VY3 VY2 VY1
0: Depending on the status of terminal
X1-X5 (without VY6-8)
1: depending on the output function
status
F17.28=xxxxxxx0: the VY1 status is the same as the actual input status of X1.
The status of the virtual output terminal VY1 is synchronized with that of the actual input
terminal X1. This can be applied in programming of multiple functions such as status
confirmation or enabling of one switch.
F17.28=xxxxxxx1: the VY1 status depends on the selected function status of the
function code F17.19.
The status of the virtual output terminal depends on the set function status, and its main
output is for software programming. The PID can be controlled via “reaching the upper
limit of PID feedback” as follows: outputting the signal “19: reach the upper limit of PID
feedback” through the virtual output terminal VY1 (F17.19=19), collecting it through the
virtual input terminal VX1 and then setting the VX1 function to “41: process PID pause”
(F17.00=41).
Note: The D7 bit of the VY8 option must be set to 1. That is, the VY8 function is always
dependent on the output function status.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F17.37
Virtual input
terminal status
VX8 VX7 VX6 VX5 VX4 VX3 VX2 VX1
000
00000
×
0: Invalid