User Manual of EM730/EM730E Series Inverter
99
1: host (Modbus protocol broadcast transmission)
F10.07
Data sent by
host
0: output frequency
1: set frequency
2: output torque
3: set torque
4: PID setting
5: output current
1
〇
F10.08
Proportional
factor of
slave
reception
0.00-10.00 (multiple)
1.00
●
F10.09
Host sending
interval
0.000-30.000
s
0.200
●
F10.10
Communicati
on protocol
option
0: Modbus-RTU protocol
0
×
F10.56
Options of
485
EEPROM
writing
0-10: default operation (for commissioning)
11: writing not triggered (available after commissioning)
0
〇
F10.57
Enabling of
SCI sending
timeout
resetting
0:invalid resetting
1: valid resetting
1
●
F10.58
Delay time of
SCI sending
timeout
resetting
110~10000
mS
150
●
F10.59
SCI response
option
0: Reply to both read and write commands
1: Reply to write commands only
2: No reply to both read and write commands
0
〇
F11
User-selected parameter group
F11.00
User-selected
parameter 1
The displayed content is Uxx.xx, which means that the
Fxx.xx function code is selected When the function code
F11.00 is enabled, the keyboard displays U00.00,
indicating that the first selected parameter is F00.00.
U00.00
●
F11.01
User-selected
parameter 2
U00.01
●
F11.02
User-selected
parameter 3
U00.02
●
F11.03
User-selected
parameter 4
U00.03
●
F11.04
User-selected
parameter 5
U00.04
●
F11.05 User-selected
U00.07
●