User Manual of EM730/EM730E Series Inverter
344
10
Register value Hi (F19.03)
01
11
Register value Lo (F19.03)
2C
12
Register value Hi (F19.04)
00
13
Register value Lo (F19.04)
00
14
Register value Hi (F19.05)
00
15
Register value Lo (F19.05)
00
16
CRC check Lo
53
17
CRC check Hi
5B
* Tail
≥3.5 characters (idle)
2)
Check whether the line is connected.
Send:
01 08 00 00 AA 55 5E 94
Return:
01 08 00 00 AA 55 5E 94 (normal)
Return:
01 88 04 47 C3 (exception, assuming a slave protection)
Send the invoice to
Normal Return
Exception Return
* Frame header
≥3.5 characters (idle)
1 Address
01 Address
01
Address
01
2 Function
08 Function
08
Function code
88
3 Sub-function code Hi 00 Sub-function code Hi
00
Exception code
04 (assumption)
4 Sub-function code Lo 00 Sub-function code Lo
00
CRC check Lo
47
5 Data Hi
AA Data Hi
AA CRC check Hi
C3
6 Data Lo
55 Data Lo
55
7 CRC check Lo
5E CRC check Lo
5E
8 CRC check Hi
94 CRC check Hi
94
* Tail
≥3.5 characters (idle)
3)
Change the carrier frequency (F00.23) to 4.0kHz.
(use the function code 0x06 as such
function codes are expected to be stored in EEPROM after change)
Send:
01 06 00 17 00 28 39 D0
Return:
01 06 00 17 00 28 39 D0 (normal)
Return:
01 86 04 43 A3 (exception, assuming a slave protection)
Send the invoice to
Normal Return
Exception Return
* Frame header
≥3.5 characters (idle)
1 Address
01 Address
01 Address
01
2 Function code
06 Function code
06 Function code
86
3 Register address Hi
00 Register address Hi
00 Exception code
04 (assumption)
4 Register address Lo
17 Register address Lo
17 CRC check Lo
43
5 Register value Hi
00 Register value Hi
00 CRC check Hi
A3
6 Register value Lo
28 Register value Lo
28
7 CRC check Lo
39 CRC check Lo
39