User Manual of EM730/EM730E Series Inverter
267
Function code Function code name
Parameter description
Unit
Default
setting
Attribute
F16.01
Set length
1 - 65535 (F16.13=0)
0.1 - 6553.5 (F16.13=1)
0.01 - 655.35 (F16.13=2)
0.001 - 65.535 (F16.13=3)
m
1,000
●
F16.02
Pulses per meter
0.1 - 6553.5
100.0
●
F16.13
Set length resolution
0:1m
1:0.1m
2:0.01 m
3:0.001m
0
〇
EM730/EM730E series inverters have a fixed-length counting function, as shown in Fig.
7-40. The length counting function is performed by entering the length information from the
digital input terminal in the pulse form and then setting the related function code. The final
length count information can be outputted by the digital output terminal for other purposes (e.g.
DI/VX input as the stop command). Users can also view the real-time length count via F18.34.
The length resolution can be set by F16.13. In case of any change in the length resolution,
F16.01 will change accordingly. For example, if F16.13 is set to 0:1m, the setting range of
F16.01 is 1-65535m.
Pulses per meter α
(0.1~6553.5) p/m
DO “length reached”
output 16# function
Pulse count
CntIn
Length 11
Lgth
DI “length clear” input
38# function
Length pulse
information
Length clear
signal
Clear to 0
Set length 1
(1-65535)m
≥
Reset
DI “length count” input 37#
function
HDI “high-speed length count”
input 38# function
“Length
reached” signal
Length
information
Sensor
Divider
Comparator
F18.34
Fig. 7-40 Block Diagram of Fixed-length Counting
Principle of fixed-length counting: The length detection sensor converts the length
information into pulse information. The DI terminal collects the number
N
of input pulses.
The length
1
N
l
is calculated based on the set function code “Pulses per meter”
and