User Manual of EM730/EM730E Series Inverter
40
grounding terminal output
AI1
Analog voltage
input
-10V to 10V, 50kΩ input impedance, bipolar
analog voltage input
AI2
Analog
current/voltage
input
Current or voltage type
Input range: 0/4-20mA or 0-10V
Analog output
M1
Analog
voltage/current
output
0-10V/0-20mA; output accuracy: ±2%
Digital input
port
X1
Multi-function
input terminal
Program the corresponding terminals by
setting function codes, to realize the input
control of the set functions.
The input terminal supports PNP and NPN
input modes, and the default mode is the NPN
input mode.
X5 can also be used as the high-frequency
pulse input, with the input frequency up to
100kHz.
X2
X3
X4
X5
Multi-function
digital output
Y1
Open collector
output terminal
It can be programmed as the multi-function
output terminal.
YCM
Common side of Y
terminal
The common side YCM of Y terminal and the
common side COM of the digital input
terminal are independent of each other.
Communication
A+
RS485
communication
terminal
positive terminal of RS485 differential signal
A-
negative terminal of RS485 differential
signal
Relay output
EA
Relay output
terminal
EA-EC: Normally open
EB-EC: Normally closed
EB
EC
External
RJ45
External keyboard For the external operation panel