User Manual of EM730/EM730E Series Inverter
148
on the
motor
type
F01.06
Motor winding
connection
0:Y
1:Δ
Depending
on the
motor
type
〇
F01.07
Rated power
factor of motor
0.600
~
1.000
Depending
on the
motor
type
〇
F01.08 Motor efficiency 30.0
~
100.0
%
Depending
on the
motor
type
〇
The above function codes are the nameplate parameters of the asynchronous motor. When
the motor is connected to the inverter for the first time, regardless of VF control or vector
control, the above parameters must be correctly set according to the motor nameplate before
operation.
When the rated power (F01.01) of the motor is changed, the values of F01.03 to F01.08 of
the inverter will change automatically. Pay attention to this during operation.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F01.09
Stator resistance
of asynchronous
motor
1-60000 (rated power of motor: ≤ 75 kW)
0.1-6000.0 (rated power of motor: >
75kW)
mΩ
Depending
on the
motor
type
〇
F01.10
Rotor resistance
of asynchronous
motor
1-60000 (rated power of motor: ≤ 75 kW)
0.1-6000.0 (rated power of motor: >
75kW)
mΩ
Depending
on the
motor
type
〇
F01.11
Leakage
inductance of
asynchronous
motor
0.01 to 600.00 (rated power of motor: ≤ 75
kW)
0.001 to 60.000 (rated power of motor: >
75 kW)
mH
Depending
on the
motor
type
〇
F01.12
Mutual
inductance of
asynchronous
motor
0.1 to 6000.0 (rated power of motor: ≤ 75
kW)
0.01 to 600.00 (rated power of motor: > 75
kW)
mH
Depending
on the
motor
type
〇