User Manual of EM730/EM730E Series Inverter
190
Output voltage
0
Rated voltage of
motor
Set rise time
VF separation
voltage
Actual rise time
Time t
Fig. 7-20 Rise Time Description of VF Separation Voltage
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F05.10
Compensation gain of
V/F stator voltage drop
0.00 - 200.00
%
100.00
●
It is used to compensate for the voltage drop caused by the stator resistor and wire, and
improve the low-frequency load capacity.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F05.11
V/F slip compensation
gain
0.00 - 200.00
%
100.00
●
F05.12
V/F slip filtering time
0.00 - 10.00
s
1.00
●
As the load increases, the rotor speed of the motor will decrease. To make the rotor speed
of the motor close to the synchronous speed under rated load, slip compensation can be enabled.
When the motor speed is less than the target value, the set value of F05.11 can be increased.
★
: In the case of F05.11=0, slip compensation is invalid. This parameter is valid only for the
asynchronous motor.
The slip is 100% during the quick start with large inertia and 0 when the frequency reaches
the set value. Quick increase or decrease of the output frequency will cause overvoltage or
overcurrent. F05.12 filtering can slow down the rise of voltage and current.
Function
code
Function code name Parameter description
Unit
Default
setting
Attribute
F05.13
Oscillation
suppression gain
0 - 20000
100
●
F05.14 Oscillation
0.00-600.00
Hz
55.00
●