User Manual of EM730/EM730E Series Inverter
271
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F16.08
Setting of cumulative
running arrival time
0-65535; 0: disable the
protection when the running
time is up
h
0
〇
Set the total cumulative running time. If the cumulative running time (F12.17) reaches or
exceeds the total cumulative running time (F16.08), please contact the agent for maintenance.
★
After this parameter is set, the inverter may fail to work normally. Be careful to set
this parameter.
Function code Function code name
Parameter description
Unit
Default
setting
Attribute
F16.09
Factory password
0 - 65535
XXXXX
●
Factory password.
★
After this password is set, the inverter may fail to work normally. Be careful to set this
password.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F16.10
Analog output
percentage
corresponding to
the count value 0
0.00-100.00
%
0.00
〇
F16.11
Analog output
percentage
corresponding to
the set count value
0.00-100.00
%
100.00
〇
The analog output is set as the offset of count and length output.
Analog output
0
F16.11
F16.10
F16.01/F16.03
Count/length
Fig. 7-17 Schematic Diagram of Analog Output of Count and Length
7.18
Virtual I/O Function Parameter Group of F17 Group
The standard EM730/EM730E series inverter is equipped with eight virtual multi-function