meaning. 100.00% is the percentage to the set value of F00.16 (maximum frequency).
F00.05=5: High-frequency pulse input (X5)
The auxiliary frequency B is determined by HDI (percentage) * F00.16.
For the details of AI1-AI2 and X5, refer to the F00.04 description. They have the same
meaning. 100.00% is the percentage to the set value of F00.16 (maximum frequency).
F00.05=6 or 7: auxiliary frequency communication setting
The auxiliary frequency B depends on the communication and others.
If the master-slave communication (F10.05=1) is enabled and the inverter works as the
slave (F10.06=0), the auxiliary frequency B is set to “700FH (master-slave
communication setting) * F00.16 (maximum frequency) * F10.08 (slave receiving
proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%,
as
detailed in
For general communication (F10.05=0):
a.
F00.05=6
, the auxiliary frequency B is set to “7002H (communication setting of the
auxiliary channel frequency B) *
F00.16 (maximum frequency)”;
b.
F00.05=7
, the auxiliary frequency B is set to “7016H (communication setting of the
auxiliary channel frequency B)”.
The 7002H data range is -100.00% to 100.00%, and the 7002H data range is 0.00 to
F00.16 (maximum frequency), as detailed in Table 12-31.
F00.05=8: digital potentiometer setting
In the speed mode, the
auxiliary frequency B
is set directly by the digital potentiometer.
See the F00.04 description for details.
F00.05=10: process PID
The auxiliary frequency B depends on the process PID function output, as detailed in 7.10.
This is usually applied in on-site closed-loop process control, such as the constant-pressure
closed-loop control and constant-tension closed-loop control.
F00.05=11: Simple PLC
The auxiliary frequency B depends on the simple PLC function output,
multi-segment group (F08) and simple PLC parameter group
1.
The same physical channel (AI1 or AI2) cannot be selected for the main