User Manual of EM730/EM730E Series Inverter
229
F09.34
Multi-segment
PID setting 3
0.0 to PID setting feedback range
F09.03
0.0
●
PID settings are determined in conjunction with the setting of the function code F09.00. The
EM730/EM730E series inverter has a multi-segment PID setting function, and its switching
conditions are mainly dependent on the input functions “15: multi-segment PID terminal 1” and
“16: multi-segment PID terminal 2”, as detailed in Table 7-16.
Table 7-18 Details of Multi-segment PID Setting Function
Method
Setting
Scope
PID Setting
16
15
F09.00
Invalid Invalid
0
F09.01
0.0 - F09.03
0.00% - 100.00%
1
AI1
-100.00% - 100.00%
-100.00% - 100.00%
2
AI2
-100.00% - 100.00%
-100.00% - 100.00%
6
485
-100.00% - 100.00%
-100.00% - 100.00%
Invalid
Valid
--
F09.32
0.0 - F09.03
0.00% - 100.00%
Valid
Invalid
--
F09.33
0.0 - F09.03
0.00% - 100.00%
Valid
Valid
--
F09.34
0.0 - F09.03
0.00% - 100.00%
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F09.35
Upper limit of
feedback voltage
Lower limit of feedback voltage to
10.00
V
10.00
●
F09.36
Lower limit of
feedback voltage
0.00 to upper limit of feedback
voltage
V
0.00
●
The upper and lower limits of the feedback voltage can be used for automatic material
cutoff detection in winding applications. They represent the upper and lower limits of material
cutoff, respectively. Due to the particularity of winding applications, F09.35 and F09.36 can be
used to reflect the real sensor boundaries, which is more conducive to the system stability.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F09.37
Options of integral
action within the
set change time of
PID
0: Always calculate the integral term
1: Calculate the integral term after
the F09.21 set time is reached
2: Calculate the integral term when
the error is less than F09.38
0
●
F09.38
Input deviation of
integral action
within the set
change time of PID
0.00-100.00
%
30.00
●